Appendix A Troubleshooting

Using Control Builder
Software to Diagnose
Problems

All communication between the ProcessLogix controller and the
1757-ABRIO module is via exchange blocks. If these exchange blocks
are producing errors or do not seem to be working properly, check
these items:

Path from the ProcessLogix controller to 1757-ABRIO module is
correct

1757-ABRIO tag name is correct

If you see error codes on your exchange blocks, in Knowledge
Builder, refer to Knowledge Builder>R500>Troubleshooting and
Maintenance Guide>Fault Codes>Exchange Block ERRCODE Fault
Codes.

Troubleshooting
1757-ABRIO Module
Communications

If the Data in the various Tag Storage files in your controller is not
what you expect, try the following possible solutions.

Check that the 1757-ABRIO module is active. If it is not active,
your controller is probably not in Run mode.

Confirm that the 1757-ABRIO tags referenced in your message
commands or exchange blocks exactly match the tag names in
the 1757-ABRIO module.

In the AbRioCfg software, right-click on the Tag Name, select
Monitor Tag, and confirm that 1757-ABRIO module is seeing the
correct data.

Both 1757-ABRIO tag name read and write data should match
the data in your controller.

Still having a problem?

Try sending data to and reading data from an I/O Module.

1. Put the controller (ProcessLogix or ControlLogix) into program

or inactive mode (or inhibit the ControlLogix controller in
RSLogix 5000 software).

The 1757-ABRIO module goes inactive.

2. Put the 1757- ABRIO module into Forced Active Mode, select

Actions>Forced Active Mode from the toolbar in AbRioCfg
software.

3. Select Flag Write from the tabs in the bottom right window.