Rockwell Automation 1757-ABRIO Process Remote I/O (RIO) Communication Interface Module User Manual

Page 130

Advertising
background image

128

Publication 1757-UM007D-EN-P - December 2008

Chapter 9 Accessing HART Data

5. If you have not already done so, create tags to accept the data

from the HART commands and map the 1770-HT1 module to
those tags.

The 1770-HT1 module occupies an entire numeric read,
flag-read or text-read tag.

6. After you select HART command 1, Read Primary Variable, from

the command list, select an offset for the location where the data
will be stored in the HART Data tags you have or will create.

7. Click Execute.

The Execution results are shown, to confirm that you are
receiving the desired data.

8. To have the data read repeatedly and attached to the

1757-ABRIO tag, click Add Cyclic.

9. Save the configuration and download it to the 1757-ABRIO

module.

TIP

Do not add write commands as cyclic commands.