Chapter 2 Configure the 1757-ABRIO Module
The 1757-ABRIO module sends messages to all possible racks
and builds the network rack configuration from the responses. It
displays a list of the racks it found in the network tree.
If you expand a rack, the partial racks that make up that rack
number are displayed.
7. If you are using 1771 remote I/O modules,
a. Right-click the rack in the network tree and select Enter Rack
Switch Setting.
The Select Rack Setting dialog box opens.