Module info tab, Backplane tab, Module info tab backplane tab – Rockwell Automation 1757-ABRIO Process Remote I/O (RIO) Communication Interface Module User Manual

Page 141

Advertising
background image

Publication 1757-UM007D-EN-P - December 2008

139

Troubleshooting Appendix A

Module Info Tab

Backplane Tab

Item

Description

Vendor

Allen-Bradley

Product Type

Communications Adapter

Product Code

107

Revision

Matches the firmware revision level of the module.

Serial Number

Matches the serial number on the module

Product Name

57ABRIO

Status Section

contains information about the connection status, including:

Major fault

Minor fault

Internal state

Configured

Owned

Module Identity

Refresh

Updates information on the screen

Item

Description

ControlBus Status

displays backplane faults

ControlBus Parameters

The Multicast CRC error threshold is fixed at 8.

The Transmit Retry Limit defaults to 45 but can be edited.

Chassis

The Chassis area contains information that relates to the
chassis, not the module.

It contains the rack Revision, Serial Number, Size, and the
1757-ABRIO module slot number.

Error Counters

These refer to communications across the backplane.

They should all be 0.

Status

The Status at the bottom of the screen indicates the
status of the connection to the module.

Advertising