Configure the 1757-ABRIO Module Chapter 2
As illustrated in the 1/2-slot addressing table below, the controller
addresses 1/2 of an I/O module slot as one I/O group. For example,
for a chassis at rack 1, starting I/O group 0, a block transfer module in
the first slot would be at address rack 1, I/O group 0, slot 0. A module
in the next slot would be at rack 1, I/O group 2, slot 0.
Configuring Block Transfer
Modules
When you add a block transfer module, the configuration dialog box
for that module opens. The contents of the dialog box are specific to
each module type.
See
Supported 1771 Modules on page 83
information on configuring individual modules.
To edit the configuration for a module, double-click the module in the
network tree, or right-click the module and select Configure.
1/2-Slot Addressing
Slot in chassis
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Rack
1
1
1
1
2
2
2
2
3
3
3
3
4
4
4
4
I/O Group
0
2
4
6
0
2
4
6
0
2
4
6
0
2
4
6
Slot
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
TIP
You cannot change the location of a module in the
configuration once you have created it. You must delete the
module and create a new one at the new location.