Publication 1757-UM007D-EN-P - December 2008

25

Configure the 1757-ABRIO Module Chapter 2

As illustrated in the 1/2-slot addressing table below, the controller
addresses 1/2 of an I/O module slot as one I/O group. For example,
for a chassis at rack 1, starting I/O group 0, a block transfer module in
the first slot would be at address rack 1, I/O group 0, slot 0. A module
in the next slot would be at rack 1, I/O group 2, slot 0.

Configuring Block Transfer
Modules

When you add a block transfer module, the configuration dialog box
for that module opens. The contents of the dialog box are specific to
each module type.

See

Supported 1771 Modules on page 83

or the online help for

information on configuring individual modules.

To edit the configuration for a module, double-click the module in the
network tree, or right-click the module and select Configure.

1/2-Slot Addressing

Slot in chassis

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

Rack

1

1

1

1

2

2

2

2

3

3

3

3

4

4

4

4

I/O Group

0

2

4

6

0

2

4

6

0

2

4

6

0

2

4

6

Slot

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

TIP

You cannot change the location of a module in the
configuration once you have created it. You must delete the
module and create a new one at the new location.