Chapter 5 Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module

4. Select the Source Element.

If you are writing to the 1757-ABRIO module, this is the
ControlLogix controller tag.

If you are reading from the 1757-ABRIO module, this is the
name of the tag in the 1757-ABRIO module.

The 1757-ABRIO module must return different data types to
ProcessLogix and ControlLogix controllers. For example, to read
a tag with name FlagRead, you would create a MSG instruction
with Source Element set to FlagRead[100].

5. Type the Number of Elements.

This is usually the number from the table on

page 68

. You can

select a size smaller than the maximum if not all of the elements
in the 1757-ABRIO module tag have been mapped.

6. Select the Destination Element.

TIP

IMPORTANT

If you are reading flag read tags using a ControlLogix controller,
you must append [100] to the 1757-ABRIO tag name. This tells
the 1757-ABRIO module that the message is coming from a
ControlLogix controller.

Use this tag

To

All_Analog_Read

Read data from input modules.

The tag is listed under Numeric Read Tags.

All_Flag_Read[100]

Flag read for status and digital data.

This is the message needed to get to analog
data.