10. Click 1757-ABRIO and click Next.

11. Expand the RSLinx Tree window to the location of the

1757-ABRIO module you wish to flash.

12. Select the module icon and click OK.

13. Confirm new revision for this update and click Next.

14. At the Summary window, click Finish.

15. To confirm the flash, click Yes.

16. Click OK.

If this update is successful, the Update Status window displays
the following message in green:

Update Complete. Please verify this new firmware update before
using the target device in its intended application.

17. Click OK and then click Cancel at the Welcome to ControlFLASH

Setup window.

18. Click Yes to end the configuration session.

Using NTools with ProcessLogix Software

On a ProcessLogix system, if the module firmware is at 1.2 or greater,
use the following procedure to update the module firmware using
NTools.

1. On the ProcessLogix Server, click Start>Run.

2. Type >ntools -c -u<.

3. To launch the Network Tools application, click OK.

4. Click OK at the warning about monitoring through Control

Builder software.

5. To initiate the network scan, click Resume.

6. Select the appropriate CNB or ENET icon.

7. Select the module to be updated in the chassis graphic.