Rockwell Automation 1757-ABRIO Process Remote I/O (RIO) Communication Interface Module User Manual

Page 149

Advertising
background image

Publication 1757-UM007D-EN-P - December 2008

147

Operational Comparison Between the 1757-ABRIO Module and a PLC-5 System Appendix B

Analog input voltage or current out
of valid over/under range for
channel configuration

Underrange or overrange bit for the channel is set

Input data for the channel in the tag is set to NaN

Set status bit.

Write NaN (Not a Number) to one
element of a numeric write tag from
a ProcessLogix controller

Value that has NaN sets the output to the configured
fault value

The block transfer continues to update

The remaining values in the tag continue to be written
correctly

Overrange bit for the channel is set

N/A

Write to or read from tag that
doesn't exist

Message gets an error status

DDE or OPC server item has bad quality

N/A

Write beyond end of tag

Message gets an error indicating the length or offset is
incorrect

DDE or OPC server item has bad quality

N/A

Write to or read from a tag that has
one (faulted) module mapped to it

Read or write message succeeds

Data from faulted input module is set to NaN

State of outputs on faulted output module depend on
the module configuration

N/A

Write to or read from a tag that has
multiple modules mapped to it, only
one module faulted

Read or write message succeeds

Data for non-faulted modules continues to update
correctly.

N/A

Read from or write to tag that has
nothing mapped to it

Read or write message fails, empty tags are not
downloaded to the 1757-ABRIO module.

N/A

OPC/DDE reads or writes tags but
control program has died or gone
away

1757-ABRIO module continues in ACTIVE mode

The output values are the last values written by the
control program, or the values written by DDE/OPC

N/A

(1)

In a ProcessLogix file, seen as NaN.
In an RSLogix 5000 file, seen as 1.#QNAN (the controller has a function that detects this)
In the ABRIO Monitor, seen as 1.#QNB.

Exception Conditions Comparison Between a PLC-5 System and a 1757-ABRIO Module

Exception Condition Message

From 1757-ABRIO Perspective

From the PLC-5 Perspective