Appendix B Operational Comparison Between the 1757-ABRIO Module and a PLC-5 System

.

Equivalent Modes

1757-ABRIO
Module

PLC-5
Controller

Description

ACTIVE

Run

Data is transferred and diagnostics are
enabled.

INACTIVE

Program

Inputs are updated and outputs are treated the
same as PLC-5 Program mode.

CONFIG

Program

Inputs are held and outputs are treated the
same as PLC-5 Program mode.

FORCED ACTIVE

Inputs are updated and outputs are set by the
user through AbRioCfg software.

TIP

Any data “read tag” refers to data being read by a controller.

Any data “write tag” refers to data being written by a controller.

Normal Operational Comparison Between a PLC-5 System and a 1757-ABRIO Module

1757-ABRIO ACTIVE or
PLC-5 RUN Modes

From the PLC-5 Perspective

From the 1757-ABRIO Perspective

Digital inputs

Digital output data updates. Data update in the
PLC data table is asynchronous to the I/O update,
based on the PLC I/O scan.

Digital input data updates (in the 1757-ABRIO
module) based on the scan list. Data updates by the
controller asynchronously when the tag is read by the
controller.

Digital outputs

Digital input data updates. Data update in the PLC
data table is asynchronous to the I/O update,
based on the PLC I/O scan.

Digital output data updates (in the 1757-ABRIO
module) based on the scan list. Data updates by the
controller asynchronously when the tag is read by the
controller.

Block transfer read data

Updates when the block transfer instruction
executes. Block transfers to the local rack are
faster than block transfers to the 1757-ABRIO
module.

Updates the 1757-ABRIO module tag when the block
transfer cycle executes based on the scan list and
user configured Block Transfer Update time. Updates
in the controller when the tag data is exchanged.

Block transfer write data

Updates on the module when the block transfer
instruction executes. Block transfers to the local
rack are faster than block transfers to 1757-ABRIO
module.

Updates on the 1757-ABRIO module when the control
process exchanges data. Updates on the module
when the block transfer cycle executes.

1757-ABRIO INACTIVE and
or PLC-5 Program Mode

From the PLC-5 Perspective

From the 1757-ABRIO Perspective

Digital inputs

Digital input data updates. Data update in the PLC
data table is asynchronous to the I/O update.

Digital input data updates in the 1757-ABRIO module.
Data does not update in the host controller since tags
are not being read.

Digital outputs

Digital output data does not update.

Digital output data does not update.

Block transfer read data

Block transfers do not execute.

Block transfers do not execute.

Block transfer write data

Block transfers do not execute.

Block transfers do not execute.