Publication 1757-UM007D-EN-P - December 2008

149

Appendix

D

Tag Descriptions for Scheduled Data in
RSLogix 5000 Software

When you create an exclusive owner or input only connection,
several tags are automatically created for the each 1757-ABRIO
module. For example, if your 1757-ABRIO module is located in the
supervisory rack, slot 3, then the configuration tag associated with it
would be Local:3:C.

Configuration Tag

The configuration tag gets created when you configure the
1757-ABRIO module as a 1756-MODULE, but the contents of the
configuration tag are not used by the 1757-ABRIO module.

I and O Tags

The I and O tags are associated with the digital I/O data. The input
tag also contains rack global status. The following tables show how
the tag contents correspond to the racks.

Generated Tag Extensions

Tag
Extension

Description

C

Configuration tag, created but not used

I

Digital input data tag

O

Digital output data tag

S

Status tag

Input Tags

Address

Description

Local:<slot>:I.Data[0]

Rack global status, 0 if all configured racks are
communicating with no errors, FFFF hex otherwise.

Local:<slot>:I.Data[1]

Rack global status, 0 if all configured racks are
communicating with no errors, FFFF hex otherwise.

Local:<slot>:I.Data[2]

Rack 1, I/O group 0 inputs

Local:<slot>:I.Data[3]

Rack 1, I/O group 1 inputs

...

Local:<slot>:I.Data[9]

Rack 1, I/O group 7 inputs