Appendix A Troubleshooting

Using RSLogix 5000 to
Diagnose Problems

Right-click the module while online in RSLogix 5000 software to
display the Module Properties dialog box. This may help in
diagnosing some problems, especially connection errors.

General Tab

Connection Tab

The Inhibit Module checkbox breaks the exclusive ownership
connection between the 1757-ABRIO module and the ControlLogix
controller. If you would like to download to the 1757-ABRIO module
without putting the controller in Program mode, check Inhibit
Module. Once you are done updating the 1757-ABRIO module,
uncheck Inhibit Module and your connection will be re-established.

Item

Description

Type

1756-MODULE Generic 1756 Module

Vendor

Allen-Bradley

Name

Defined when you configured the module.

Description

Defined when you configured the module.

Comm Format

Matches what you defined when module was configured.

Slot

Matches what you defined when module was configured.

Connection
Parameter

Matches what you defined when module was configured.

If this box is checked

Then

Major Fault on Controller if
Connection Fails While in Run
Mode

This causes the module to fault the controller if the
connection between the ControlLogix controller and the
module fails.