I/o data – Rockwell Automation 1757-ABRIO Process Remote I/O (RIO) Communication Interface Module User Manual

Page 98

Advertising
background image

96

Publication 1757-UM007D-EN-P - December 2008

Chapter 8 Supported 1771 Modules

3. Set the gain and offset for each channel.

See the Thermocouple/Millivolt Input Module User Manual,
publication

1771-6.5.130

, for more information.

4. If desired, enable real-time sampling (RTS) and set the sampling

rate, from 0.1 to 3.1 seconds.

This becomes the effective data update rate and may override
the update rate if the update rate is smaller.

5. Set the Update Time for the module’s block transfer.

The range is 1 to 16382 milliseconds. This sets the requested
update rate; the actual rate depends on the baud rate, the
number of racks on the RIO network and whether block
transfers are running to other modules in the same rack.

I/O Data

The 1771-IXE module returns 9 words of floating point data.

This data can be mapped to a numeric read tag.

1771-IXE Module I/O Data

Data Word

Description

0

Channel 1 data

1

Channel 2 data

2

Channel 3 data

3

Channel 4 data

4

Channel 5 data

5

Channel 6 data

6

Channel 7 data

7

Channel 8 data

8

Cold junction temperature

Advertising