Chapter 4 Configuring the ProcessLogix Controller to Access Data on the 1757-ABRIO Module
7. Set the number of values to be read or written.
a. Flag arrays, 512 max
b. Numeric arrays, 64 max
c. Text arrays, 64 max
Array Examples
8. Set the data type to be read or written.
a. Numeric arrays, set Data Type in Target Device to FLOAT32.
b. Text arrays, set the Number of String Values to 1 and the Char
Length of String Values to 64.
9. Select the Communications tab.
10. Set the Path from the ProcessLogix controller to the 1757-ABRIO
module.
or Control Builder Help for information
on entering the path.
Flag Arrays
Numeric Arrays
Text Arrays