Rockwell Automation 1757-ABRIO Process Remote I/O (RIO) Communication Interface Module User Manual

Page 56

Advertising
background image

54

Publication 1757-UM007D-EN-P - December 2008

Chapter 4 Configuring the ProcessLogix Controller to Access Data on the 1757-ABRIO Module

7. Set the number of values to be read or written.

a. Flag arrays, 512 max

b. Numeric arrays, 64 max

c. Text arrays, 64 max

Array Examples

8. Set the data type to be read or written.

a. Numeric arrays, set Data Type in Target Device to FLOAT32.

b. Text arrays, set the Number of String Values to 1 and the Char

Length of String Values to 64.

9. Select the Communications tab.

10. Set the Path from the ProcessLogix controller to the 1757-ABRIO

module.

See the tip on

page 72

or Control Builder Help for information

on entering the path.

Flag Arrays

Numeric Arrays

Text Arrays