Publication 1757-UM007D-EN-P - December 2008

Chapter 5 Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module

The Module Properties dialog box opens.

6. Type a Name and a Description for the module, if desired.

7. Set the Slot number for the module in the ControlLogix chassis.

8. For the Comm Format, select Input Data - INT - With Status.

9. Select the following values for the Connection Parameters.

Assembly
Instance

Size

Input

1

250

Output

3

N/A

Configuration

4

0

Status Input

5

10

Status Output

6

N/A