Chapter

6

Accessing Data through a DDE or OPC Server

Introduction

This chapter describes how to access data on the module using a DDE
or OPC Server.

Accessing Data from a DDE
or OPC Server

You can access data on the 1757-ABRIO module directly using a DDE
or OPC server such as RSLinx software, without the intervention of a
host controller.

Configuring a Topic in RSLinx Software

Use the following procedure to use RSLinx software as a DDE or OPC
server to access data on the 1757-ABRIO module.

1. Start RSLinx software

2. Select DDE/OPC Topic Configuration from the main menu.

3. Click New to create a new DDE or OPC topic, and give the topic

a name.

4. Select the Data Source tab and browse to the 1757-ABRIO

module.

5. Select the Data Collection tab.

6. Set the Processor Type to Logix5000.

7. Check Polled Messages and set the poll period to an appropriate

value.

8. Un-check Unsolicited Messages.

9. Leave the remaining values at their default values and click

Apply.

10. Select the Advanced Communication tab.

11. Select the Communications Driver you are using.