E-32 Application Examples

The 1747-SCNR and 1747-ACNR15 modules are shown as nodes
1 and 3, respectively. The three I/O modules are under the
1747-ACNR15 in slots 1 through 3 of the 1747-ACNR15 chassis.

3. To establish a 16-bit rack connection to the 1747-ACNR15

chassis, right-click the 1747-ACNR15 module and choose Insert
Connection.

You see the following window:

Note that addresses in the Connection Properties window are
already displayed in the fields. To have RSNetWorx for
ControlNet software choose the next available, valid I/O or
M-file addresses for all connections:

a. Click the Auto Address Preferences button.

b. Click the box next to Enable Automatic Addressing on Insert

so that a check mark appears in the box.

c. Click OK.

The Connection Name by default is Discrete 16 Bit Exclusive
Owner. This is the 16-bit rack connection we want. The first
available I/O addresses are I:3.1 and O:3.1, where the
1747-SCNR is in slot 3 of the processor chassis. The first
available starting I/O addresses have been placed into the Input
Address and Output Address fields by RSNetWorx for ControlNet
software, because automatic addressing was previously selected
in the Auto Address Preference screen.