Rockwell Automation 1747-SCNR ControlNet Scanner Module Reference Manual User Manual
Page 18

Publication 1747-RM623D-EN-P - June 2006
1-6 Install and Connect the ControlNet Scanner
.
For detailed information on planning and installing your ControlNet
system, see the table for a list of related publications.
If Your Network Supports
Connect the Tap’s Straight or Right-angle
Connector
Nonredundant media
To the channel A connector on the scanner—channel B is
not used.
(1)
(1)
We recommend using channel A for nonredundant media.
Redundant media
From the trunk-cable A to channel A on the scanner
andfrom trunk-cable B to channel B on the scanner
Publication
Publication Number
ControlNet Coax Tap Installation Instructions
1786-IN007
ControlNet Network Access Cable Installation Instructions
1786-TD006
Industrial Automation Wiring and Grounding Guidelines
1770-IN041
Redundant Media
Nonredundant Media
30802
A
A
B
Remove the tap’s dust cap—located on the straight or right-angle connector—and set it aside.