Publication 1747-RM623D-EN-P - June 2006

Prepare to Use the ControlNet Scanner 2-7

Module Status (M1:e.1)

See Troubleshooting for probable causes and recommended actions.

ControlNet Status (M1:e.2)

See the table that contains bit numbers and their descriptions.

Value

Description

0x20

The scanner is not configured.

0x21

The current configuration is not valid.

0x22

Connections are configured, but no connections are established.

0x23

Connections are configured, but only 25% are successfully established.

0x24

Connections are configured, but only 50% are successfully established.

0x25

Connections are configured, but only 75% are successfully established.

0x26

All configured connections are established.

0x42

The node address is set to 00. This caused the scanner to erase network and
connection configuration stored in flash.

0x43

The scanner detected a network error due to a ControlNet cable problem or there
are no other nodes on the network.

0x44

The scanner has the same ControlNet address as another device on the network.

Bit 0-2

Channel A status

Value

LED State

000

Off

001

Green

010

Flashing green/off

011

Flashing red/off

100

Flashing red/green

101

Alternating red/off

110

Alternating red/green

111

Red

Bit 3

Reserved

Bit 4-6

Channel B status

Value

LED State

000

Off

001

Green

010

Flashing green/off

011

Flashing red/off

100

Flashing red/green

101

Alternating red/off

110

Alternating red/green

111

Red

Bit 7-15

Reserved