E-38 Application Examples

The Connection Properties window will close and the Scanlist
Configuration window appears and looks as follows:.

You have successfully configured your two connections to read/write
data between the SLC processor and the remote ControlNet chassis.
All that remains is to save the configuration to the network keeper,
which in this case is the 1747-SCNR scanner.

1 . Click the Save icon or click the File menu and then Save.

You are prompted to Optimize and re-write schedule for all
connections.

2. Click OK.

3. Click YES to the warning message.

Your network configuration information is written to the
network keeper.

The display on the front of your 1747-SCNR scanner should
show an image of a full glass next to the word I/O. This
indicates that all configured connections have been successfully
downloaded to the scanner. In addition, the A and OK LEDs
should be solid green and the B LED should be off, unless you
are using the redundant media option, which is not being used
in this example. The 1747-ACNR15 module should be displaying
that it is active (ACTV) and its LEDs should be solid green for A
and OK and the B LED should be off.