E-16 Application Examples

Configure a Module Connection

Next, we need to configure a module connection for the 1746-NIO4V
module, 2 input/2 output module.

1 . Right-click the 1746-NIO4V module in the Scanlist Configuration

window.

2. Select Insert Connection.

A Connection Properties window appears.

3. Choose Exclusive Owner for the connection name.

For this example, we must choose M-file addresses for our 2
input/2 output analog module. The first available M-file
addresses are M1:3.3 and M0:3.3. Words 0 through 2 are
reserved. The next available Status Address is M1:3.600/02, since
bits 0 and 1 are used for the rack connection. The Connection
Properties window for the module connection should look like
the following: