Rockwell Automation 1747-SCNR ControlNet Scanner Module Reference Manual User Manual
Page 99
![background image](/manuals/579671/99/background.png)
Publication 1747-RM623D-EN-P - June 2006
Application Examples E-21
6. Choose Edit Chassis and verify that the chassis configuration is
as follows:
• slot 0: 1747-ACNR15
• slot 1: 1746-IA16
• slot 2: 1746-OB16
• slot 3: 1746-NI8
If the chassis is not already configured, manually configure it by
dragging the appropriate modules from the list on the right to
the proper slot on the left of the chassis configuration screen.
When this is complete, click APPLY and then OK.
Configure a Rack Connection
We are now ready to configure the necessary ControlNet connections
so we can read/write data from the SLC processor to the discrete I/O
modules and to the analog I/O module.
1 . Right-click the 1747-SCNR scanner and choose Scanlist
Configuration.
You are prompted to enter the Edit mode.
2. Click YES.
You see the following screen: