E-42 Application Examples

This rung simply gives the following rung a false-to-true transition every 1 second.

This rung copies up to 64 words beginning with N12:0 to the SCNR for transfer to the Basic module on ControlNet.

This rung completes the handshaking between the SLC processor and ultimately the Basic module to accomplish the CALL 23.

L

COP

9

Timer On Delay
Timer

T4:1

Timer Base

0.01

Preset

100<

Accum

86<

DN

TON

T4:1

EN

DN

0000

Copy File
Source

#N12.0

Dest

#M0:3.11

Length

64

DN

COP

T4:1

0001

CALL 23 output
handshake bit

M0:3.3

6

CALL 23 input
handshake bit

CALL 23 output
handshake bit

U

M1:3.3

M0:3.3

6

0002

6

This rung copies up to 64 words of data received from the Basic module, when the handshake bit M1:3.3/9 becomes set. When data is
received by the Basic module in PRT2, the CALL 22 transfers it to the SCNR and ultimately to the SLC Processor.

CALL 23 input
handshake bit

M1:3.3

9

0003

Copy File
Source

#M1:3.11

Dest

#N13.0

Length

64

CALL 23 output
handshake bit

M0:3.3

10

1747-SCNR RUN/IDLE
Bit

O:3

1747-SCNR

0004

0005

END