Rockwell Automation 1747-SCNR ControlNet Scanner Module Reference Manual User Manual

Page 84

Advertising
background image

Publication 1747-RM623D-EN-P - June 2006

E-6 Application Examples

Words I:3.0 and O:3.0 are reserved. Note that the input data
from the 1746-IA16 module is found in the processor’s input
image word I:3.3, the output data written to the 1746-OB16
module is from the processor’s output image word O:3.2, and
the input data from the 1746-IV16 module is in the processor’s
input image word I:3.5.

You must also enter a value in the Status Address field. This field
supplies Connection Status information to the processor. The
starting bit address for this field must be an even number,
because two consecutive bits are used as status for each
connection. The even numbered bit indicates whether the
connection is open or closed and the odd numbered bit
indicates whether the connection is in normal operation or Idle
mode. In this example, the address chosen is the first available
bit pair, M1:3.600/00.

You have successfully configured a rack connection to the remote
chassis to communicate with the discrete I/O modules. At this point,
you may also configure the state of the outputs in the remote
ControlNet Chassis when the processor is placed into the Program
mode or if communications is lost to the remote chassis. This is
optional. The default is to turn all outputs off when one of the two
conditions occur. To select other options follow these steps.

a. Click the Advanced tab in the Connection Properties window.

IMPORTANT

There is a two-word offset for input data for rack
connections. Therefore, for this example, the input data
for the input module in slot 1 of the remote 1747-ACNR15
chassis is written to I:3.3 in the SLC processor’s input
image and the input module in slot 3 is written to I:3.5.

The starting input address configured in RSNetWorx for
ControlNet software for this rack connection was I:3.1, but
I:3.1 and I:3.2 are used for status information. The Input
Size of 5 is shown in the Connection Properties screen.

The actual input data begins after the two words of status
information. I:3.4 is not used in this example because an
output module resides in slot 2. Also, note that there is no
offset for the outputs in a rack connection. O:3.2 is the
output image word written to the output module located
in slot 2 of the 1747-ACNR15 chassis. O:3.1 is also not
used in this example because an input card is in slot 1.

Advertising