B-2 Use CIP Messaging to Access Local Database and ControlNet Data Files
Assembly Object Instance Numbers Supported for Get and
Set Member on Data Attribute
The following table lists assembly object instance numbers
supported for Get and Set Member services.
These rules apply to all Set Member or Get Member services on
the Assembly Object.
• Set Member and Set Attribute services on the discrete Input
data file are rejected if the SLC processor is in Run mode
(no write access).
• Set Member and Set Attribute services on the discrete
Output data file are always rejected (no write access).
• Set Member and Set Attribute services on the M0 and M1
files are always accepted (regardless of SLC processor
mode).
SLC File
Word Offset
Contents
Assembly
Object
Instance
Number
Member
Number
Range
Input
0…31
ControlNet
Input Data
6
1…32
Output
0…31
ControlNet
Output Data
5
(1)
(1)
Instance 5 does not support Set Member service (no write access).
1…32
M1
0…607
ControlNet
Input Data
8
1…608
M0
0…1650
ControlNet
Output Data
7
1…1651