Rockwell Automation 1747-SCNR ControlNet Scanner Module Reference Manual User Manual

Page 50

Advertising
background image

Publication 1747-RM623D-EN-P - June 2006

5-6 Troubleshoot

See the table that describes how the status indicator is behaving, the
cause of the behavior, and the action you should take.

and

Probable Cause Recommended Action

Off

No power

No action required or apply power.

Steady red

Faulty unit

Cycle power or reset unit. If fault persists, contact a
Rockwell Automation representative or distributor.

Alternating red/green Self-test

No action required.

Alternating red/off

Incorrect node
configuration or
duplicate
ControlNet node
address

Check network address and other ControlNet
configuration parameters.

or

Probable Cause Recommended Action

Off

Channel disabled

Program network for redundant media, if required.

Steady green

Normal operation No action required.

Flashing green/off

Temporary
network errors

• Check media for items such as broken

cables, loose connectors, and missing
terminators.

Flashing red/off

Media fault

• Check media for broken cables, loose

connectors, missing terminators, etc.

No other nodes
present on the
network

Add other nodes to the network.

Flashing red/green

Incorrect node
address

Change 1747-SCNR node address so that it is less
than or equal to SMAX.

(1)

Incorrect network
configuration

Reconfigure ControlNet network so that SMAX

1

is

greater than or equal to 1747-SCNR node address.

(1)

SMAX is the highest node address on a ControlNet network that can transmit scheduled data.