Publication 1747-RM623D-EN-P - June 2006

2-6 Prepare to Use the ControlNet Scanner

Module Status (I:e.0)

1747-SCNR M1 File

Bit 0

1747-SCNR Module Faulted.

Bit 1

1747-SCNR Communication Module Fault
The 1747-SCNR scanner is not on line. See M1 word 2 (M1:e2) for the
ControlNet network status.

Bit 2

1747-SCNR Connection Fault
There is a fault in at least one scheduled connection.

Bit 3-7

Reserved.

Bit 8

Reset 1747-SCNR Module Acknowledge
The 1747-SCNR scanner will complement this bit each time the scanner is reset
due to complementing the Reset module command bit (O:e.0/8 where e is the
scanner slot number). See Example of Reset Bit Management.

Bit 9

Disable ControlNet Scheduled Connections Acknowledge
The 1747-SCNR scanner will set this bit when the Disable ControlNet
Scheduled Connections Command bit is set (O:e.0/9) and all scheduled
connections have been closed. The 1747-SCNR scanner will clear this bit when
the Disable ControlNet Scheduled Connections Command bit is cleared.

Bit 10

Scanner Mode
The 1747-SCNR scanner clears this bit when it is in idle mode. The 1747-SCNR
Scanner sets this bit when it is in run mode.

Bit 11-15 Reserved.

Word
Offsets

Word
Size

ControlNet
Transfer Mode

Contents

Description

0

1

N/A

Reserved

Reserved for future use.

1

1

N/A

Module
Status (See
the next page
“Module
Status”)

Value indicating the current
operational status of the module. See
the Troubleshooting for probable
causes and recommended actions.

2

1

N/A

ControlNet
Status (See
the next page
“ControlNet
Status”)

Value indicating the current channel
LEDs.

3-255

253

Scheduled

ControlNet
Input Data

You can map scheduled input data in
this area using RSNetWorx for
ControlNet software.

256-599 344

N/A

Reserved

Reserved.

600-607 8

N/A

Connection
Status

Bit field reporting scheduled
connections status.
Two consecutive bits per scheduled
connection:
Connection State
(Even bit numbers)
1:connection opened
0:connection closed
Remote Device Mode
(Odd bit numbers)
1:remote device is in run mode
0:remote device is in idle mode