1-8 Install and Connect the ControlNet Scanner

SLC 500 I/O Configuration
for the 1747-SCNR Module

Select the I/O card. If you do not have an I/O card, complete the
following procedure.

Open RSLogix 500 software and use the following procedure to
configure the 1747-SCNR module.

In the RSLogix 500 project Window:

1 . Open the I/O Configuration window.

2. Select the 1747-SCNR slot number.

3. Select the 1747-SCNR module from the current available cards

list. If it is not available, perform the following steps:

a. Choose the other ..Requires I/O card type ID line in the

Current cards available list.

b. In the Other type I/O Card window, type 13628.

c. On the line associated with the scanner slot, the I/O

Configuration window will report the following:

OTHER I/O Module- ID Code = 13628

d. Double-click the scanner line to open the Advanced I/O

Configuration window.

e. Set M0 Length to 1651 (decimal) and M1 Length to 608

(decimal).

4. Close the I/O Configuration and Advanced I/O Configuration

windows.

ATTENTION

Use the 1786-CP cable when connecting a
scanner to the network through a NAP. Using
a commercially-available RJ-style cable could
result in network failure.