D-2 Example of Reset Bit Management
I:3
2
Use a timer to re-enable the module after a 4
seconds delay.
1
If the module in slot 3 is not enabled, no access to
the module is allowed
Enable the module 4 seconds after the reset
bit has been set.
During a reset operation, use a TND or any
other instruction to avoid executing all
instructions that access the module.
Set the Reset bit in Output Command Word
TND
Disable the 1747-SCNR module in Slot 3
XOR
S2:11
U
3
Timer On Delay
Timer
T4:0
Timer Base
1.0
Preset
4
Accum
0
Your Precondition2
0
3
Bitwise Exclusive OR
Source A
O:3.0
Source B
256
Length
O:3.0
TON
S2:11
EN
DN
T4:0
DN
L
S2:11
3
Example: If the module in slot 3 is faulted, reset it.
Your Precondition1
41558
IMPORTANT
In this ladder example, when S2:11\e, I:e\0 or O:e.0
are used, e is the 1747-SCNR slot number in the SLC
rack. If you reuse this example and your module is
not in slot 3, update all instructions with the current
appropriate number.