Rockwell Automation 1747-SCNR ControlNet Scanner Module Reference Manual User Manual

Page 53

Advertising
background image

Publication 1747-RM623D-EN-P - June 2006

Local Database Access Using PLC-5 MSG Instructions A-3

The following example illustrates how a PLC-5 ladder program can
read or write the 1747-SCNR Local Database using the MSG
instruction. The steps in this process correspond to the steps in the
illustrations.

1 . The ladder programmer inserts a MSG instruction into the ladder

program.

2. This message instruction sends five words from the PLC-5 N7

data file, starting at offset 0, to remote 1747-SCNR Local
Database file offset 10 (N7:10). The destination node is 22.

3. The PLC-5 processor is put into RUN mode. Then the PLC-5

processor opens an unscheduled connection to the 1747-SCNR
module and messages are exchanged.

4. The SLC 500 ladder program reads 20 words of 1747-SCNR Local

Database in slot 0 offset 700: #M0:1.700.

5. Elements from the PLC-5 N7 file are available in the SLC 500 N11

file, starting at address N11:10.

IMPORTANT

When the #M0.e.yyyy address is used in ladder
instructions, e is the 1747-SCNR slot number in the SLC
rack. If you reuse this example, and your module is not in
slot number one, update all instructions with the current
appropriate number.

Advertising