Publication 1747-RM623D-EN-P - June 2006

CIP Client Management C-13

SLC 500 Processor: N7 Data File (hex)

RSLogix 500

Detail:

N7:0 = 0x8000:Control word with bit EN set
N7:1 = 0x08:Target MAC ID - Node 8
N7:2 = 0x200:Timeout 512 ms
N7:3 = 0x0:Complex IOI size - Not used
N7:4 = 0x19:Set Member service code
N7:5 = 0x04:Target Class code - Identity object class
N7:6 = 0x07:Target Instance number - Instance 7: M0 File
N7:7 = 0x03:Target Attribute number - Data
N7:8 = 0x2BD:Target Member number - 701, one based offset, M0 File
Local Database word 700
N7:9 = 0x41:Command Data size - 65 = 1 data length word + 64 words
of actual data, copy to M0:1.1100
N7:10 to N7:75:Data copied to M0:1.1100

The length contained in N7:9 includes the size word of N7:10,

plus the number of data words to be sent.