Work with the ControlNet Explicit Message Instruction 4-7
Scanner Status, Error, and Error Description on the General Tab
The Scanner Code displays the explicit message status returned by the
scanner. A scanner code of 0 means no errors. See the CEM
Instruction Scanner Codes table for a list of other valid scanner codes.
CEM Instruction Scanner Codes
Scanner Code
Description of Scanner Status
201H
Invalid command data size
202H
Internal fault detected
204H
Invalid service code
205H
Invalid IOI size
206H
Invalid CIP request block contents
207H
CIP message request timeout
208H
CIP timeout value too small