Work with the ControlNet Explicit Message Instruction 4-7

Scanner Status, Error, and Error Description on the General Tab

The Scanner Code displays the explicit message status returned by the
scanner. A scanner code of 0 means no errors. See the CEM
Instruction Scanner Codes table for a list of other valid scanner codes.

CEM Instruction Scanner Codes

Scanner Code

Description of Scanner Status

201H

Invalid command data size

202H

Internal fault detected

204H

Invalid service code

205H

Invalid IOI size

206H

Invalid CIP request block contents

207H

CIP message request timeout

208H

CIP timeout value too small