Publication 1747-RM623D-EN-P - June 2006

Troubleshoot 5-5

ControlNet Status indicators may behave in these ways and display
these additional color schemes as described:

• Steady – indicator is on continuously in the defined state.
• Alternating – the two indicators alternate between the two

defined states at the same time (applies to both indicators
viewed together). The two indicators are always in opposite
states (out of phase).

• Flashing – the indicator alternates between the two defined

states (applies to each indicator viewed independent of the
other). If both indicators are flashing, they must flash together
(in phase).

Sequence OK

Indicator

Alpanumeric
Display

Module Status
Word (M1 file)

Description

Probable Cause

Recommended Action

Run time

Flashing
Green

SIGM

N/A

A scanner signature
mismatch has been
detected. The
1747-SCNR scanner
signature does not
match the signature
stored in the active
keeper.

The scanner is not able
to start any scheduled
communication to
remote devices. Only
unscheduled
communication is
possible.

Module is not
configured properly.

Use RSNetWorx for
ControlNet software to
schedule the existing
configuration.
Use RSNetWorx for
ControlNet software to
download a new
configuration.

Errors

Off

None

N/A

Module is not
communicating.

Power supply fault.

Check power supply,
cable connectors, and
seat module firmly in
chassis.

Flashing
Green

N/A

0x43

Network error.

Cable error or no other
nodes on the network.

Verify network cabling.

Red

(Scrolling
display
showing fault
details)

N/A

Module faulted.

Internal error
detected.

Record fault details and
contact Rockwell
Automation
representative or
distributor.

Flashing
Red

A#00
FLSH
CFG
ERAS

0x42

Module erased network
and connection
configuration stored in
flash.

Network node
address is set to 00.

Power down the module
and change the address
switches.

DUPL
A#XX

0x44

Duplicate node address. Another device with

the same ControlNet
address is on the link.

Power down the
1747-SCNR module and
change the network
address switches to a
correct node.