Rockwell Automation 1747-SCNR ControlNet Scanner Module Reference Manual User Manual

Page 90

Advertising
background image

Publication 1747-RM623D-EN-P - June 2006

E-12 Application Examples

If the chassis is not already configured, manually configure it by
dragging the appropriate modules from the list on the right to
the proper slot on the left of the chassis configuration screen.
When this is complete, click APPLY and then OK.

Configure a Rack Connection

We are now ready to configure the necessary ControlNet connection
so we can read/write data from the SLC processor to the discrete I/O
modules and to the analog I/O module.

1 . Right-click the 1747-SCNR scanner and choose Scanlist

Configuration.

You are prompted to enter the Edit mode.

2. Click YES.

You see the following screen:

The 1747-SCNR and 1747-ACNR15 modules are shown as nodes
1 and 3, respectively. The three I/O modules are under the
1747-ACNR15 module in slots 1 through 3 of the 1747-ACNR15
chassis.

3. To establish a 16-bit rack connection to the 1747-ACNR15

chassis, right-click the 1747-ACNR15 module and choose Insert
Connection.

Advertising