Publication 1747-RM623D-EN-P - June 2006

E-56 Application Examples

As you can see, the two 1747-SCNR ControlNet scanners are
shown as nodes 1 and 2. To establish a scheduled peer-to-peer
connection so node 1 can send/produce 50 words of data for
node 2:

4. Right-click the 1747-SCNR scanner at node 2.

5. Choose Insert Connection.

You see the following window:

Note that addresses in the Connection Properties window are
already displayed in the fields. To have RSNetWorx for
ControlNet software choose the next available, valid I/O or
M-file addresses for all connections:

a. Click the Auto Address Preferences button.

b. Click the box next to Enable Automatic Addressing on Insert

so that a check mark appears in the box.

c. Click OK.