Publication 1747-RM623D-EN-P - June 2006

Install and Connect the ControlNet Scanner 1-5

3. Insert the module into the slot you have selected, noting that we

recommend that you insert the 1747-SCNR scanner as close to
the chassis power supply as possible.

4. Apply firm and even pressure to seat the module in the I/O

chassis backplane connectors.

5. Restore power to the SLC chassis.

Connect to a ControlNet
Network

Connect the 1747-SCNR scanner to a ControlNet network via a tap
with a 1 m (39.4 in.) drop cable. Four taps are available from
Rockwell Automation, Inc., as shown in the figure.

After terminating your segments, connect your node to the network.

Straight T-tap

Straight Y-tap

1786-TPS

1786-TPYR

1786-TPR

1786-TPYS

Right-angle Y-tap

Right-angle-Tap

20094

IMPORTANT

Allen-Bradley ControlNet taps contain passive
electronics and must be purchased from Rockwell
Automation for the network to function properly.

WARNING

If you connect or disconnect the ControlNet cable
with power applied to this module or any device
on the network, an electrical arc can occur. This
could cause an explosion in hazardous location
installations. Be sure that power is removed or the
area is nonhazardous before proceeding.