Using Real-Time Clock and Memory Modules

The MicroLogix 1100 controller has a built-in real-time clock (RTC). You can
order a memory module as an accessory.

One type of memory module is available for use with the MicroLogix 1100
controller.

Real-Time Clock Operation

Operation at Power-up and Entering a Run or
Test Mode

At power-up and when the controller enters a run or test mode, the values
(date, time and status) of the RTC are written to the RTC Function File in the
controller.

The following table indicates the accuracy of the RTC for various
temperatures.

TIP

For more information on “Real-Time Clock Function
File” and “Memory Module Information File”, refer to
the MicroLogix 1100 Programmable Controllers
Instruction Set Reference Manual, publication
1763-RM001.

Catalog Number

Function

Memory Size

1763-MM1

Memory Module

128 KB

RTC Accuracy

Ambient Temperature

Accuracy

(1)

(1)

These numbers are maximum worst case values over a 31-day month.

0 °C (32 °F)

-13...-121 seconds/month

25 °C (77 °F)

54...-5 seconds/month

40 °C (104 °F)

29...-78 seconds/month

55 °C (131 °F)

-43...-150 seconds/month