Recommended surge suppressors – Rockwell Automation 1763 MicroLogix 1100 Programmable Controllers User Manual User Manual

Page 47

Advertising
background image

Publication 1763-UM001D-EN-P - March 2011

Wiring Your Controller 45

Recommended Surge Suppressors

Use the Allen-Bradley surge suppressors shown in the following table for use
with relays, contactors, and starters.

Recommended Surge Suppressors

Device

Coil Voltage

Suppressor Catalog
Number

Bulletin 509 Motor Starter
Bulletin 509 Motor Starter

120V AC
240V AC

599-K04

(1)

599-KA04

(1)

(1)

Varistor – Not recommended for use on relay outputs.

Bulletin 100 Contactor
Bulletin 100 Contactor

120V AC
240V AC

199-FSMA1

(2)

199-FSMA2

(2)

(2)

RC Type – Do not use with Triac outputs.

Bulletin 709 Motor Starter

120V AC

1401-N10

(2)

Bulletin 700 Type R, RM Relays

AC coil

None Required

Bulletin 700 Type R Relay
Bulletin 700 Type RM Relay

12V DC
12V DC

199-FSMA9

Bulletin 700 Type R Relay
Bulletin 700 Type RM Relay

24V DC
24V DC

199-FSMA9

Bulletin 700 Type R Relay
Bulletin 700 Type RM Relay

48V DC
48V DC

199-FSMA9

Bulletin 700 Type R Relay
Bulletin 700 Type RM Relay

115-125V DC
115-125V DC

199-FSMA10

Bulletin 700 Type R Relay
Bulletin 700 Type RM Relay

230-250V DC
230-250V DC

199-FSMA11

Bulletin 700 Type N, P, or PK Relay

150V max, AC or DC

700-N24

(2)

Miscellaneous electromagnetic
devices limited to 35 sealed VA

150V max, AC or DC

700-N24

(2)