Recommended surge suppressors – Rockwell Automation 1763 MicroLogix 1100 Programmable Controllers User Manual User Manual
Page 47

Publication 1763-UM001D-EN-P - March 2011
Wiring Your Controller 45
Recommended Surge Suppressors
Use the Allen-Bradley surge suppressors shown in the following table for use
with relays, contactors, and starters.
Recommended Surge Suppressors
Device
Coil Voltage
Suppressor Catalog
Number
Bulletin 509 Motor Starter
Bulletin 509 Motor Starter
120V AC
240V AC
599-K04
(1)
599-KA04
(1)
(1)
Varistor – Not recommended for use on relay outputs.
Bulletin 100 Contactor
Bulletin 100 Contactor
120V AC
240V AC
199-FSMA1
(2)
199-FSMA2
(2)
(2)
RC Type – Do not use with Triac outputs.
Bulletin 709 Motor Starter
120V AC
1401-N10
(2)
Bulletin 700 Type R, RM Relays
AC coil
None Required
Bulletin 700 Type R Relay
Bulletin 700 Type RM Relay
12V DC
12V DC
199-FSMA9
Bulletin 700 Type R Relay
Bulletin 700 Type RM Relay
24V DC
24V DC
199-FSMA9
Bulletin 700 Type R Relay
Bulletin 700 Type RM Relay
48V DC
48V DC
199-FSMA9
Bulletin 700 Type R Relay
Bulletin 700 Type RM Relay
115-125V DC
115-125V DC
199-FSMA10
Bulletin 700 Type R Relay
Bulletin 700 Type RM Relay
230-250V DC
230-250V DC
199-FSMA11
Bulletin 700 Type N, P, or PK Relay
150V max, AC or DC
700-N24
(2)
Miscellaneous electromagnetic
devices limited to 35 sealed VA
150V max, AC or DC
700-N24
(2)