Rockwell Automation 1763 MicroLogix 1100 Programmable Controllers User Manual User Manual

Page 163

Advertising
background image

Publication 1763-UM001D-EN-P - March 2011

Specifications 161

Standard DC Input Filter Settings (Inputs 4 and higher)

Nominal Filter Setting (ms)

ON Delay (ms)

OFF Delay (ms)

Maximum Frequency (Hz)
50% Duty Cycle

Minimum Maximum

Minimum Maximum

0.500

0.090

0.500

0.020

0.500

1.0 kHz

1.000

0.500

1.000

0.400

1.000

0.5 kHz

2.000

1.100

2.000

1.300

2.000

250 Hz

4.000

2.800

4.000

2.700

4.000

125 Hz

8.000

(1)

5.800

8.000

5.300

8.000

63 Hz

16.000

11.000

16.000

10.000

16.000

31 Hz

(1) This is the default setting.

Relay Contact Ratings

Maximum Volts

Amperes

Amperes
Continuous

(1)

Volt-Amperes

Make

Break

Make

Break

240V AC

15.0 A

1.5 A

5.0 A

(2)

/3.0 A

3600 VA

360 VA

120V AC

30.0 A

3.0 A

5.0 A

(2)

/3.0 A

3600 VA

360 VA

125V DC

0.22 A

(3)

1.0 A

28 VA

24V DC

1.2 A

(3)

2.0 A

(1) 5.0 A for UL 508

3. 0A for UL 1604, Class 1, Division 2, Hazardous Locations, Groups A, B, C, D

(2) 3.0 A above 40 °C.(104 °F)

(3) For DC voltage applications, the make/break ampere rating for relay contacts can be determined by dividing 28 VA by

the applied DC voltage. For example, 28 VA/48V DC = 0.58A. For DC voltage applications less than 14V, the
make/break ratings for relay contacts cannot exceed 2A.

Working Voltage (1763-L16AWA)

Description

1763-L16AWA

Power supply input to backplane isolation Verified by one of the following dielectric tests: 1836V AC for 1 s or 2596V DC for 1 s

265V AC Working Voltage (IEC Class 2 reinforced insulation)

Input group to backplane isolation

Verified by one of the following dielectric tests:1517V AC for 1 s or 2145V DC for 1 s

132V AC Working Voltage (IEC Class 2 reinforced insulation)

Input group to input group isolation

Verified by one of the following dielectric tests:1517V AC for 1 s or 2145V DC for 1 s

132V AC Working Voltage (basic insulation)

Output group to backplane isolation

Verified by one of the following dielectric tests: 1836V AC for 1 s or 2596V DC for 1 s

265V AC Working Voltage (IEC Class 2 reinforced insulation)

Output group to output group isolation

Verified by one of the following dielectric tests: 1836V AC for 1 s or 2596V DC for 1s

265V AC Working Voltage (basic insulation) 150V AC Working Voltage (IEC Class 2 reinforced
insulation).

Advertising