20 Installing Your Controller

EMC Directive

This product is tested to meet Council Directive 89/336/EEC
Electromagnetic Compatibility (EMC) and the following standards, in whole
or in part, documented in a technical construction file:

EN 61000-6-4
EMC - Part 6-4: Generic Standards - Emission Standard for Industrial
Environments

EN 61000-6-2
EMC - Part 6-2: Generic Standards - Immunity for Industrial
Environments

This product is intended for use in an industrial environment.

Low Voltage Directive

This product is tested to meet Council Directive 73/23/EEC Low Voltage, by
applying the safety requirements of EN 61131-2 Programmable Controllers,
Part 2 - Equipment Requirements and Tests.

For specific information required by EN 61131-2, see the appropriate sections
in this publication, as well as the following Allen-Bradley publications:

Industrial Automation Wiring and Grounding Guidelines for Noise Immunity,
publication 1770-4.1

Guidelines for Handling Lithium Batteries, publication AG-5.4

Automation Systems Catalog, publication B115

Installation Considerations

Most applications require installation in an industrial enclosure (Pollution
Degree 2

(1)

) to reduce the effects of electrical interference (Over Voltage

Category II

(2)

) and environmental exposure. Locate your controller as far as

possible from power lines, load lines, and other sources of electrical noise such
as hard-contact switches, relays, and AC motor drives. For more information
on proper grounding guidelines, see the Industrial Automation Wiring and
Grounding Guidelines
publication 1770-4.1.

(1)

Pollution Degree 2 is an environment where normally only non-conductive pollution occurs except that
occasionally temporary conductivity caused by condensation shall be expected.

(2)

Overvoltage Category II is the load level section of the electrical distribution system. At this level, transient
voltages are controlled and do not exceed the impulse voltage capability of the products insulation.