Rockwell Automation 1763 MicroLogix 1100 Programmable Controllers User Manual User Manual
Page 172
Advertising
Publication 1763-UM001D-EN-P - March 2011
170 Specifications
Relays Used vs. Maximum Current per Relay (24V DC) 1762-OX6I
Module Load Ratings 1762-OX6I
Volts (max.)
Controlled Load (Current) per Module (max.)
240V AC
6 A
120V AC
12 A
(1)
(1) Current per relay limited to 6 A at ambient temperatures above 40 °C (104.°F).
125V DC
11.5 A
24V DC
30 A
(2)
(2) 24 A in ambient temperatures above 40 °C (104.°F). Limited by ambient temperature and
the number of relays controlling loads. See below.
1
2
3
3
4
5
6
7
8
4
5
6
Number of Relays Controlling Loads
Maximum
Curr
ent per Relay (Am
p
s)
Ambient Temperature
below 40 °C (104.°F)
Ambient Temperature
above 40 °C (104.°F)
Advertising