170 Specifications

Relays Used vs. Maximum Current per Relay (24V DC) 1762-OX6I

Module Load Ratings 1762-OX6I

Volts (max.)

Controlled Load (Current) per Module (max.)

240V AC

6 A

120V AC

12 A

(1)

(1) Current per relay limited to 6 A at ambient temperatures above 40 °C (104.°F).

125V DC

11.5 A

24V DC

30 A

(2)

(2) 24 A in ambient temperatures above 40 °C (104.°F). Limited by ambient temperature and

the number of relays controlling loads. See below.

1

2

3

3

4

5

6

7

8

4

5

6

Number of Relays Controlling Loads

Maximum

Curr

ent per Relay (Am

p

s)

Ambient Temperature
below 40 °C (104.°F)

Ambient Temperature
above 40 °C (104.°F)