Communication Connections 85

Typical 3-Node Network (Channel 0 Connection)

Recommended Tools

To connect a DH-485 network to additional devices, you need tools to strip
the shielded cable and to attach the cable to the AIC+ Advanced Interface
Converter. We recommend the following equipment (or equivalent):

DH-485 Communication Cable

The suggested DH-485 communication cable is either Belden #3106A or
#9842. The cable is jacketed and shielded with one or two twisted-wire pairs
and a drain wire.

One pair provides a balanced signal line and one additional wire is used for a
common reference line between all nodes on the network. The shield reduces
the effect of electrostatic noise from the industrial environment on network
communication.

The communication cable consists of a number of cable segments
daisy-chained together. The total length of the cable segments cannot exceed
1219 m (4000 ft). However, two segments can be used to extend the DH-485

TERM

A

B

COM

SHLD

CHS GND

TX

TX

PWR

TX

DC SOURCE

CABLE

EXTERNAL

A-B

PanelView

PanelView 550

MicroLogix 1100

1761-CBL-AM00
or 1761-CBL-HM02

1747-CP3 or
1761-CBL-AC00

RJ45 port

1761-CBL-AS09
or 1761-CBL-AS03

CH0

Working with Cable for DH-485 Network

Description

Part Number

Manufacturer

Shielded Twisted Pair Cable

#3106A or #9842

Belden

Stripping Tool

Not Applicable

Not Applicable

1/8” Slotted Screwdriver

Not Applicable

Not Applicable