Publication 1763-UM001D-EN-P - March 2011

160 Specifications

Surge current per point:

•peak current
•maximum surge duration
•maximum rate of repetition at 30 °C (86 °F)
•maximum rate of repetition at 55 °C (131 °F)

•4.0 A
•10 ms
•once every second
•once every 2 seconds

•Not applicable
•Not applicable
•Not applicable
•Not applicable

Turn-on time, max.

0.1 ms

6 µs

Turn-off time, max.

1.0 ms

18 µs

Repeatability, max.

n/a

2 µs

Drift, max.

n/a

1 µs per 5 °C (9 °F)

(1) Output 2 and 3 are designed to provide increased functionality over the other FET outputs. Output 2 and 3 may be used like the other FET transistor outputs, but in addition,

within a limited current range, they may be operated at a higher speed. Output 2 and 3 also provide a pulse train output (PTO) or pulse width modulation output (PWM)
function.

BBB FET Output Specifications

Description

General Operation

High Speed Operation

(1)

(Output 2 and 3 Only)

AC Input Filter Settings

Nominal Filter Setting (ms)

ON Delay (ms)

OFF Delay (ms)

Minimum Maximum

Minimum Maximum

8

2

20

10

20

High-Speed DC Input Filter Settings (Inputs 0 to 3)

Nominal Filter Setting (ms) ON Delay (ms)

OFF Delay (ms)

Maximum Counter Frequency (Hz)
50% Duty Cycle

Minimum Maximum

Minimum Maximum

00125

0.005

0.0125

0.003

0.0085

40.0 kHz

(2)

0.025

0.005

0.025

0.005

0.025

20.0 kHz

0.075

0.040

0.075

0.045

0.075

6.7 kHz

0.100

0.050

0.100

0.060

0.100

5.0 kHz

0.250

0.170

0.250

0.210

0.250

2.0 kHz

0.500

0.370

0.500

0.330

0.500

1.0 kHz

1.00

0.700

1.000

0.800

1.000

0.5 kHz

2.000

1.700

2.000

1.600

2.000

250 Hz

4.000

3.400

4.000

3.600

4.000

125 Hz

8.000

(1)

6.700

8.000

7.300

8.000

63 Hz

16.000

14.000

16.000

14.000

16.000

31 Hz

(1) This is the default setting.

(2) OS Series B FRN4 or later