86 Communication Connections

network to 2438 m (8000 ft). For additional information on connections using
the AIC+, refer to the Advanced Interface Converter (AIC+) User Manual,
publication 1761-6.4.

When cutting cable segments, make them long enough to route them from one
AIC+ to the next, with sufficient slack to prevent strain on the connector.
Allow enough extra cable to prevent chafing and kinking in the cable.

Use these instructions for wiring the Belden #3106A or #9842 cable. (

See

Cable Selection Guide on page 90

if you are using standard Allen-Bradley

cables.)

Connecting the Communication Cable to the DH-485 Connector

Single Cable Connection

When connecting a single cable to the DH-485 connector, use the following
diagram.

TIP

A daisy-chained network is recommended. Do not
make the incorrect connection shown below:

Belden #3106A
or #9842

Belden #3106A or
#9842

Belden #3106A or
#9842

Connector

Connector

Connector

Incorrect

Orange with White Stripes

White with Orange Stripes

Shrink Tubing Recommended

Blue (#3106A) or
Blue with White
Stripes (#9842)

Drain Wire

6 Termination

5 A
4 B
3 Common
2 Shield
1 Chassis Ground