Rockwell Automation 1763 MicroLogix 1100 Programmable Controllers User Manual User Manual

Page 174

Advertising
background image

Publication 1763-UM001D-EN-P - March 2011

172 Specifications

General Specifications

Specification

1762-IF2OF2

1762-IF4

1762-OF4

1762-IR4

1762-IT4

Shipping weight,
approx. (with
carton)

240 g (0.53 lbs.)

235 g (0.517 lbs.)

260 g (0.57 lbs.)

220 g (0.53 lbs.)

Bus current draw,
max.

40 mA at 5V DC
105 mA at 24V DC

40 mA at 5V DC
50 mA at 24V DC

40 mA at 5V DC
165 mA at 24V DC

40 mA at 5V DC
50 mA at 24V DC

40 mA at 5V DC
50 mA at 24V DC

Analog normal
operating range

Voltage: 0…10V DC
Current: 4…20 mA

Voltage:
-10…+10V DC
Current: 4…20 mA

Voltage 0…10V DC
Current: 4…20 mA

NA

NA

Full scale

(1)

analog ranges

Voltage:
0…10.5V DC
Current: 0…21 mA

Voltage:
-10.5…+10.5V DC
Current: -21…+21
mA

Voltage:0…10.5V DC
Current: 0…21 mA

NA

NA

Resolution

12 bits (unipolar)

15 bits (bipolar)

(4)

12 bits (unipolar)

Input filter and
configuration
dependent

15 bits plus sign

Repeatability

(2)

±0.12%

(4)

±0.12%

(4)

±0.12%

(4)

±0.1 °C (±0.18 °F) for
Ni and NiFe
±0.2 °C
(±0.36 °F)…±0.2 °C
(±0.36 °F) for other
RTD inputs
±0.04 ohm for
150 ohm resistances
±0.2 ohm for other
resistances

See Table 176

Input and output
group to system
isolation

30V AC/30V DC rated working voltage

(3)

(N.E.C. Class 2 required)
(IEC Class 2 reinforced insulation)
type test: 500V AC or 707V DC for 1 minute

30V AC/30V DC rated
working voltage
(IEC Class 2
reinforced insulation)
type test: 500V AC or
707V DC for 1 minute

30V AC/30V DC
working voltage
type test: 500V AC or
707V DC for 1 minute

30V AC/30V DC
working voltage
qualification test:
720V DC for 1 minute

Vendor I.D. code

1

1

1

1

1

Product type code 10

10

10

10

10

Product code

75

67

66

65

64

(1) The over- or under-range flag comes on when the normal operating range (over/under) is exceeded. The module continues to convert the analog input up to the maximum

full scale range.

(2) Repeatability is the ability of the module to register the same reading in successive measurements for the same signal.

(3) Rated working voltage is the maximum continuous voltage that can be applied at the terminals with respect to earth ground.

(4) Only applicable to Series B I/O modules.