Calculating heat dissipation – Rockwell Automation 1763 MicroLogix 1100 Programmable Controllers User Manual User Manual

Page 238

Advertising
background image

Publication 1763-UM001D-EN-P - March 2011

236 System Loading and Heat Dissipation

Calculating Heat
Dissipation

Use the following table when you need to determine the heat dissipation of
your system for installation in an enclosure. For System Loading, take the value
from the appropriate system loading worksheets on pages 234 or 235.

Heat Dissipation

Catalog Number

Heat Dissipation

Equation or Constant

Calculation

Sub-Total

1763-L16AWA

15.2 W + (0.4 x System Loading)

15.2 W + (0.4 x ______ W)

W

1763-L16BWA

15.7 W + (0.4 x System Loading)

15.7 W + (0.4 x ______ W)

W

1763-L16BBB

17.0 W + (0.3 x System Loading)

17.0 W + (0.3 x ______ W)

W

1763-L16DWD

17.0 W + (0.3 x System Loading)

17.0 W + (0.3 x ______ W)

W

1762-IA8

2.0 W x number of modules

2.0 W x _________

W

1762-IF4

2.0 W x number of modules

2.0 W x _________

W

1762-IF2OF2

2.6 W x number of modules

2.6 W x _________

W

1762-IQ8

3.7 W x number of modules

3.7 W x _________

W

1762-IQ16

5.4 W

(1)

x number of modules

5.4 W

(1)

x _________

W

1762-IQ32T

6.8 W x number of modules (at 30.0V DC)
5.4 W x number of modules (at 26.4V DC)

6.8 W x _________ (at 30.0V DC)
5.4 W x _________ (at 26.4V DC)

W
W

1762-IR4

1.5 W x number of modules

1.5 W x _________

W

1762-IT4

1.5 W x number of modules

1.5 W x _________

W

1762-OA8

2.9 W x number of modules

2.9 W x _________

W

1762-OB8

1.6 W x number of modules

1.6 W x _________

W

1762-OB16

2.9 W x number of modules

2.9 W x _________

W

1762-OB32T

3.4 W x number of modules

3.4 W x _________

W

1762-OF4

3.8 W x number of modules

3.8 W x _________

W

1762-OV32T

2.7 W x number of modules

2.7 W x _________

W

1762-OW8

2.9 W x number of modules

2.9 W x _________

W

1762-OW16

6.1 W

(1)

x number of modules

6.1 W

(1)

x _________

W

1762-OX6I

2.8 W x number of modules

2.8 W x _________

W

1762-IQ8OW6

4.4 W x number of modules

4.4 W x _________

W

Add Sub-Totals to determine Heat Dissipation

W

(1) Only applicable to Series B I/O modules.