Publication 1763-UM001D-EN-P - March 2011
88 Communication Connections
End-of-Line Termination
MicroLogix 1100 Channel 0 to DH-485 Communication Cable Pinout
When connecting MicroLogix 1100 Channel 0 to DH-485 communication
cable pinout using an RS-232 cable, the maximum that the cable length may be
extended is 15.24 m (50 ft). Refer to the following typical pinout:
Jumper
Jumper
Belden #3106A or #9842 Cable
1219 m (4000ft) Maximum
Jumper
DTE Device
(MicroLogix
1100
Channel 0)
DCE Device (DH-485
connector)
8-Pin
6-pin
7
TXD
6
Termination
4
RXD
5
A
2
GND
4
B
1
B(+)
3
Common
8
A(-)
2
Shield
5
N.C.
1
ChassisGround
6
CTS
3
RTS