Connecting to the rs-232 port – Rockwell Automation 1763 MicroLogix 1100 Programmable Controllers User Manual User Manual

Page 78

Advertising
background image

Publication 1763-UM001D-EN-P - March 2011

76 Communication Connections

6. Press the ESC key to return to the Advanced Settings Menu screen, as

shown in

step 3

.

Connecting to the RS-232
Port

There are two ways to connect the MicroLogix™ 1100 programmable
controller to your personal computer using the DF1 protocol: using a
point-to-point connection, or using a modem. Descriptions of these methods
follow.

ATTENTION

All devices connected to the RS-232/485
communication port must be referenced to controller
ground, or be floating (not referenced to a potential
other than ground). Failure to follow this procedure
may result in property damage or personal injury.

For 1763-L16BWA controllers, the COM of the
sensor supply is also connected to chassis ground
internally. The 24V DC sensor power source should
not be used to power output circuits. It should only be
used to power input devices.

For 1763-L16BBB and 1763-L16DWD controllers,
the VDC NEUT or common terminal of the power
supply is also connected to chassis ground
internally.

Available Communication Cables

Communication Cables

Length

1761-CBL-AM00 Series C or later cables are required for Class I Div 2 applications.

45 cm (17.7 in.)

1761-CBL-AP00 Series C or later cables are required for Class I Div 2 applications.

45 cm (17.7 in.)

1761-CBL-PM02 Series C or later cables are required for Class I Div 2 applications.

2 m (6.5 ft)

1761-CBL-HM02 Series C or later cables are required for Class I Div 2 applications.

2 m (6.5 ft)

2707-NC9 Series C or later cables are required for Class I Div 2 applications.

15 m (49.2 ft)

1763-NC01 Series A or later

30 cm (11.8 in.)

Advertising