Rockwell Automation 1763 MicroLogix 1100 Programmable Controllers User Manual User Manual

Page 164

Advertising
background image

Publication 1763-UM001D-EN-P - March 2011

162 Specifications

Working Voltage (1763-L16BWA)

Description

1763-L16BWA

Power supply input to backplane isolation Verified by one of the following dielectric tests:1836V AC for 1 s or 2596V DC for 1 s

265V AC Working Voltage (IEC Class 2 reinforced insulation)

Input group to backplane isolation and
input group to input group isolation

Verified by one of the following dielectric tests: 1200V AC for 1 s or 1697V DC for 1 s

75V DC Working Voltage (IEC Class 2 reinforced insulation)

Output group to backplane isolation

Verified by one of the following dielectric tests: 1836V AC for 1 s or 2596V DC for 1 s

265V AC Working Voltage (IEC Class 2 reinforced insulation).

Output group to output group isolation

Verified by one of the following dielectric tests: 1836V AC for 1 s or 2596V DC for 1 s

265V AC Working Voltage (basic insulation) 150V Working Voltage (IEC Class 2 reinforced
insulation)

Working Voltage (1763-L16BBB)

Description

1762-L16BBB

Input group to backplane isolation and
input group to input group isolation

Verified by one of the following dielectric tests: 1200V AC for 1 s or 1697V DC for 1 s

75V DC Working Voltage (IEC Class 2 reinforced insulation)

FET output group to backplane isolation

Verified by one of the following dielectric tests: 1200V AC for 1 s or 1697V DC for 1 s

75V DC Working Voltage (IEC Class 2 reinforced insulation)

Relay output group to backplane isolation Verified by one of the following dielectric tests: 1836V AC for 1 s or 2596V DC for 1 s

265V AC Working Voltage (IEC Class 2 reinforced insulation).

Relay output group to relay output group
and FET output group isolation

Verified by one of the following dielectric tests: 1836V AC for 1 s or 2596V DC for 1 s

265V AC Working Voltage (basic insulation) 150V Working Voltage (IEC Class 2 reinforced
insulation)

Working Voltage (1763-L16DWD)

Description

1763-L16BWA

Input group to backplane isolation and
input group to input group isolation

Verified by one of the following dielectric tests: 1200V AC for 1 s or 1697V DC for 1 s

75V DC Working Voltage (IEC Class 2 reinforced insulation)

Output group to backplane isolation

Verified by one of the following dielectric tests: 1836V AC for 1 s or 2596V DC for 1 s

265V AC Working Voltage (IEC Class 2 reinforced insulation).

Output group to output group isolation

Verified by one of the following dielectric tests: 1836V AC for 1 s or 2596V DC for 1 s

265V AC Working Voltage (basic insulation) 150V Working Voltage (IEC Class 2 reinforced
insulation)