Rockwell Automation 1763 MicroLogix 1100 Programmable Controllers User Manual User Manual

Page 46

Advertising
background image

Publication 1763-UM001D-EN-P - March 2011

44 Wiring Your Controller

suppressor can also be used. See for recommended suppressors. As shown
below, these surge suppression circuits connect directly across the load device.

Suitable surge suppression methods for inductive AC load devices include a
varistor, an RC network, or an Allen-Bradley surge suppressor, all shown
below. These components must be appropriately rated to suppress the
switching transient characteristic of the particular inductive device. See the
table on 45 for recommended suppressors.

+24V DC

IN4004 Diode

Relay or Solid
State DC Outputs

24V DC common

VAC/DC

Out 0
Out 1
Out 2
Out 3
Out 4
Out 5
Out 6
Out 7

COM

(A surge suppressor
can also be used.)

Surge Suppression for Inductive AC Load Devices

Output Device

Output Device

Output Device

Varistor

RC Network

Surge
Suppressor

Advertising