Publication 1763-UM001D-EN-P - March 2011

Connecting to Networks via Ethernet Interface 217

Cables

Shielded and non-shielded twisted-pair 10/100Base-T cables with RJ45
connectors are supported. The maximum cable length between an MicroLogix
1100 Ethernet port and a 10/100Base-T port on an Ethernet hub or switch
(without repeaters or fiber) is 100 m (323 ft). However, in an industrial
application, cable length should be kept to a minimum.

Straight-through cabling

IMPORTANT

When connecting the MicroLogix 1100 Ethernet port
to a 10/100Base-T Ethernet switch, note the
following recommendations:

•

Use the auto negotiation function for both the switch port and the
MicroLogix 1100 Ethernet port

•

If you want to force to a specific speed/duplex mode, you should
force the MicroLogix 1100 Ethernet port and leave the switch in
auto negotiation mode to match speed/duplex settings of the
MicroLogix 1100. Ethernet port.

•

If you want to disable the auto negotiation function for both
ports, then you should only force both the switch and the
MicroLogix 1100 port to either 100Mbps Half-duplex or 10
Mbps/Half-duplex.
If you attempt to force both the switch and the MicroLogix1100
port to either 100 Mbps Full-duplex or 10 Mbps Full-duplex, the
Ethernet link will not be established and Ethernet
communications will not work.

TIP

The Ethernet cabling with straight-through method is
recommended as below. Do not make the incorrect
connection.

Pin

Pin Name

Cable color

1

Tx+ Orange/White

2

Tx- Orange

3

Rx+ Green/White

4

No used by 10/100Base-T

Blue

5

No used by 10/100Base-T

Blue/White

6

Rx- Green

7

No used by 10/100Base-T

Brown/White

8

No used by 10/100Base-T

Brown