Connecting to Networks via Ethernet Interface 217

Cables

Shielded and non-shielded twisted-pair 10/100Base-T cables with RJ45
connectors are supported. The maximum cable length between an MicroLogix
1100 Ethernet port and a 10/100Base-T port on an Ethernet hub or switch
(without repeaters or fiber) is 100 m (323 ft). However, in an industrial
application, cable length should be kept to a minimum.

Straight-through cabling

IMPORTANT

When connecting the MicroLogix 1100 Ethernet port
to a 10/100Base-T Ethernet switch, note the
following recommendations:

Use the auto negotiation function for both the switch port and the
MicroLogix 1100 Ethernet port

If you want to force to a specific speed/duplex mode, you should
force the MicroLogix 1100 Ethernet port and leave the switch in
auto negotiation mode to match speed/duplex settings of the
MicroLogix 1100. Ethernet port.

If you want to disable the auto negotiation function for both
ports, then you should only force both the switch and the
MicroLogix 1100 port to either 100Mbps Half-duplex or 10
Mbps/Half-duplex.
If you attempt to force both the switch and the MicroLogix1100
port to either 100 Mbps Full-duplex or 10 Mbps Full-duplex, the
Ethernet link will not be established and Ethernet
communications will not work.

TIP

The Ethernet cabling with straight-through method is
recommended as below. Do not make the incorrect
connection.

Pin

Pin Name

Cable color

1

Tx+ Orange/White

2

Tx- Orange

3

Rx+ Green/White

4

No used by 10/100Base-T

Blue

5

No used by 10/100Base-T

Blue/White

6

Rx- Green

7

No used by 10/100Base-T

Brown/White

8

No used by 10/100Base-T

Brown